The commercial electric rates for the City of Cuyahoga Falls are outlined below throughout the various schedules.

Please note that the rate schedules are subject to the general rules and regulations of the electric utility and are apt to be adjusted. All questions should be directed to the Utility Billing Department.


  1. 933.03 Schedule GSS- General Service, Small, Single Phase
  2. 933.04 Schedule GSM- General Service, Medium, Three Phase
  3. 933.05 Schedule GSL - General Service, Large
  4. 933.06 Schedule GSD- General Service, Distribution

933.03 SCHEDULE GSS- GENERAL SERVICE, SMALL, SINGLE PHASE

Available where secondary distribution lines are adjacent to the premises to be served, 933.03 Schedule GSS applies to electric service supplied at one point on one premises. This rate does not apply to standby service.

Service

Electric service alternating current, sixty hertz, and where available, single phase, nominal 120/240 volts.

Charges

Customer Charge: $23.00/Month + All KWH: $0.11468/KWH

Note: The minimum charge will equal the schedule's monthy customer fee, and that the monthly charge shall be adjusted according to the Power Cost Factor, or PCF.

Contract

A written application is required for 933.03.


933.04 SCHEDULE GSM- GENERAL SERVICE, MEDIUM, THREE PHASE

Available where secondary distribution lines are adjacent to the premises to be served, 933.04 Schedule GSM applies to electric service supplied at one point on one premises. This rate does not apply to standby service.

Service

Electric service alternating current, sixty hertz, and where available, three phase, nominal 480 volts, 240 volts or 120/208 volts.

Charges

Customer Charge: $31.00/Month + All KWH: $0.11381/KWH

Note: The minimum charge will equal the schedule's monthy customer fee, and that the monthly charge shall be adjusted according to the Power Cost Factor, or PCF.

Contract

A written application is required for 933.04.


933.05 SCHEDULE GSL - GENERAL SERVICE, LARGE

933.05 Schedule GSL is available where secondary distribution lines are adjacent to the premises to be served and where the billing demand is greater than fifty KW. This rate does not apply to standby service.

Service

Electric service alternating current, sixty hertz, and where available, three phase, four wire, 240 volts, 480 volts or 120/208 volts.

Charges
Demand Charge Rate/Kilowatt
First 100KW Demand per Month $17.20/KW
Over 100KW Demand per Month $17.20/KW
 
Energy Charge Rate/Kilowatt
First 250KWH Per KW Billing Demand $0.0635/KWH
Next 150KWH Per KW Billing Demand $0.0635/KWH
All Additional KWH $0.0635/KWH

Charges
Customer Charge: $75.00/Month

Kilowatt Billing Demand

The minimum charge shall be the demand charge. The billing demand for the month shall be the greatest of:

  1. The highest measured fifteen minute KW demand during the month.
  2. Sixty percent (60%) of the highest billing demand during the preceding eleven months.
  3. Fifty KW.

When metering capable of measuring on-peak and off-peak demands is in use, the customer's measured demand shall be the greater of the on-peak demand or twenty-five percent (25%) of the off-peak demand. On-peak periods are from 8:00 a. m. to 9:00 p.m., on normal business days. All other periods shall be off-peak.

Note: The monthly charge shall be adjusted according to the Power Cost Factor, or PCF.

Power Factor

The customer shall arrange and equip installation so that the power factor of the load at the time of maximum demand will be not less than 0.8 lagging; however, if the power factor as determined by measurement is less than 0.8, the measured demand shall be modified by the ratio of 0.8 to the measured power factor.

Metering

In the event the electric utility elects to meter the service on the high voltage side of the transformation equipment, the kilowatt-hours as registered on the meter, and read by the meter reader, will be reduced in quantity by three percent (3%) prior to calculating the monthly charge.This is known as the Special Large Rate Class.

Contract

A written application is required for 933.05


933.06 SCHEDULE GSD- GENERAL SERVICE, DISTRIBUTION

933.06 Schedule GSD is available where distribution lines are adjacent to the premises to be served. This applies to electric service supplied at one point on one premises where the demand is greater than fifty KW, and where the consumer owns and maintains all transforming, controlling, regulating, and protective equipment. This rate does not apply to standby-service.

Service

Electric service alternating current, sixty hertz, and where available, 3 phase nominal 2400/4160 volts, three phase, 4 wire, grounded or 7200/12,470 volts, 4 wire grounded.

Charges

The monthly charge per customer shall be the sum of the demand and energy charges in accordance with the following rates.

Demand Charge Rate/Kilowatt
First 100KW Demand Per Month $15.40/KW
All Over 100KW Demand Per Month $15.40/KW
 
Energy Charge Rate/Kilowatt
First 250KWH Per KW Billing Demand $0.06191/KWH
Next 150KWH Per KW Billing Demand $0.06191/KWH
All Additional KWH $0.06191/KWH

Charges
Customer Charge: $150.00/Month

Kilowatt Billing Demand

The minimum charge shall be the demand charge. The billing demand for the month shall be the greatest of:

  1. The highest measured fifteen minute KW demand during the month.
  2. Sixty percent (60%) of the highest billing demand during the preceding eleven months.
  3. Fifty KW.

When metering capable of measuring on-peak and off-peak demands is in use, the customer's measured demand shall be the greater of the on-peak demand or twenty-five percent (25%) of the off-peak demand. On-peak periods are from 8:00 a. m. to 9:00 p.m., on normal business days. All other periods shall be off-peak.

Note: The monthly charge shall be adjusted according to the Power Cost Factor, or PCF.

Power Factor

The customer shall arrange and equip installation so that the power factor of the load at the time of maximum demand will be not less than 0.8 lagging; however, if the power factor as determined by measurement is less than 0.8, the measured demand shall be modified by the ratio of 0.8 to the measured power factor.

Contract

A written application is required for 933.06.